Bidhelp
Ministry of Electronics and Information Technology
Department of Electronics and Information Technology
Not Found
PUNJAB QTY : 1254

Items - Supply of indoor type floor mounted metal clad 11kV,Installation testing and commissioning of indoor type floor mounted metal clad,Supply of Heat shrinkable type indoor end termination kit,Making Heat shrinkable type indoor end termination,Supply of 50 x 6 mm GI strip including fixing clam,Laying of 50 x 6 mm GI strip including fixing clamps,Supply of 12Cx2.5 Sqmm 1.1 KV grade XLPE,Laying of 12Cx2.5 Sqmm 1.1 KV grade,Supply of 12Cx2.5Sqmm size indoor,Making of 12Cx2.5 Sqmm Size indoor,Dismantling and removing of existing 11kV HT

Tender Details
Costs
Documents
BOQ
Item NumberItem TitleItem DescriptionItem QuantityUnit of MeasureConsignee IDDelivery Period (In number of days)
1 Supply of indoor type floor mounted metal clad 11kV Supply of indoor type floor mounted metal clad 11kV 50Hz VCB panel having two incomer of 2000A one buscoupler of 2000A along with bus riser and 8 no. of outgoing of 800A 2 no. of line PT compartment detailed as per attached technical specifications and SLD. Make of Panel and VCB Siemens Schneider ABB 1 No con26.oda.mh@gembuyer.in 196
2 Installation testing and commissioning of indoor type floor mounted metal clad Installation testing and commissioning of indoor type floor mounted metal clad 11kV panel having two incomer of 2000A one buscoupler of 2000A along with bus riser and 8 No of outgoing of 800A 50Hz VCB panel detailed as per attached technical specifications and SLD. 1 No con26.oda.mh@gembuyer.in 196
3 Supply of Heat shrinkable type indoor end termination kit Supply of Heat shrinkable type indoor end termination kit complete with all accessories including lugs neoprene bushes and interconnections earthing complete as required and as directed by EIC for the 3C x 300 sq.mm 11 KV grade XLPE insulated round armoured aluminium conductor cable . Make Raychem 3M GEE Seal Denson. 10 No con26.oda.mh@gembuyer.in 196
4 Making Heat shrinkable type indoor end termination Making Heat shrinkable type indoor end termination for 3C x 300 sq.mm 11 KV grade XLPE insulated armoured aluminium conductor cable as required and as directed by EIC. Note cable Termination or joint shall be done by certified Experienced professionals only. 9 No con26.oda.mh@gembuyer.in 196
5 Supply of 50 x 6 mm GI strip including fixing clam Supply of 50 x 6 mm GI strip including fixing clamps and inclusive of supply of all hardwares for connecting with the exisiting MS or GI earthing rod complete as required. Make Reputed. 100 Mtr con26.oda.mh@gembuyer.in 196
6 Laying of 50 x 6 mm GI strip including fixing clamps Laying of 50 x 6 mm GI strip including fixing clamps at suitable interval and accessories when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and interconnections with earth pit and equipment terminations or interconnections in an approved manner as per IS 3043 with latest amendments as required. 100 Mtr con26.oda.mh@gembuyer.in 196
7 Supply of 12Cx2.5 Sqmm 1.1 KV grade XLPE Supply of 12Cx2.5 Sqmm 1.1 KV grade XLPE insulated and overall sheathed stranded Copper conductor flat steel strip or wire armoured cables conforming to IS 7098 orPart I with latest amendments. The cables or drum shall bear ISI certification mark. Make Finolex Havells RPG Polycab Glostar Lapp KEI Rallision Note Party to submit the type test certificate for the cables. 500 Mtr con26.oda.mh@gembuyer.in 196
8 Laying of 12Cx2.5 Sqmm 1.1 KV grade Laying of 12Cx2.5 Sqmm 1.1 KV grade XLPE insulated and overall sheathed stranded Copper conductor flat steel strip or wire armoured cables conforming to IS 7098 or Part I with latest amendments on existing cable tray or surface or wall as required. 500 Mtr con26.oda.mh@gembuyer.in 196
9 Supply of 12Cx2.5Sqmm size indoor Supply of 12Cx2.5Sqmm size indoor end termination with nickel coated brass double compression gland and Cu lugs for Cu conductor XLPE insulated 1.1 KV grade cable as required Make Dowells Commet Hex 3M 16 No con26.oda.mh@gembuyer.in 196
10 Making of 12Cx2.5 Sqmm Size indoor Making of 12Cx2.5 Sqmm Size indoor end termination with nickel coated brass double compression gland and Cu lugs for Copper conductor XLPE insulated 1.1 KV grade cable as required 16 No con26.oda.mh@gembuyer.in 196
11 Dismantling and removing of existing 11kV HT Dismantling and removing of existing 11kV HT 10 VCB Panel with 2 No of Incomer 1 buscoupler 2 PT feeder and 5 No of outgoing from the foundation installed on floor or Trench channel by disconnecting of 9 No of incoming or outgoing 3Cx300 Sq.mm HT cable and including shifting of the same from existing location Ground floor HT Substation to nearby scrapyard within SCL permises. 1 No con26.oda.mh@gembuyer.in 196