WEST BENGAL QTY : 4416

Items - Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 400 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 35 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 70 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 70 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 50 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 95 Sqmm 3.5 Core.,Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 25 Sqmm 4 Core.,Excavating in Trenches not exc. 1.50 mtr wide and not exc. 1.50 mtr in depth, getting out in Soft Loose Soil complete all as specified and as directed.,Returning, Filling in including Spreading, Levelling, Waterin

Tender Details
Costs
Documents
BOQ
Item NumberItem TitleItem DescriptionItem QuantityUnit of MeasureConsignee IDDelivery Period (In number of days)
1 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 400 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 400 Sqmm 3.5 Core. 300 RM con688.ia.wb@gembuyer.in 180
2 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 35 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 185 Sqmm 3.5 Core. 135 RM con688.ia.wb@gembuyer.in 180
3 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 70 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 95 Sqmm 3.5 Core. 60 RM con688.ia.wb@gembuyer.in 180
4 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 70 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 70 Sqmm 3.5 Core. 40 RM con688.ia.wb@gembuyer.in 180
5 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 50 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 50 Sqmm 3.5 Core. 265 RM con688.ia.wb@gembuyer.in 180
6 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 95 Sqmm 3.5 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 35 Sqmm 3.5 Core. 200 RM con688.ia.wb@gembuyer.in 180
7 Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 25 Sqmm 4 Core. Supply laying and testing cable XLPE Insulated 1100 Volts grade with stranded aluminium conductor 25 Sqmm 4 Core. 70 RM con688.ia.wb@gembuyer.in 180
8 Excavating in Trenches not exc. 1.50 mtr wide and not exc. 1.50 mtr in depth, getting out in Soft Loose Soil complete all as specified and as directed. Excavating in Trenches not exc. 1.50 mtr wide and not exc. 1.50 mtr in depth, getting out in Soft / Loose Soil, complete all as specified and as directed. 239 Cum con688.ia.wb@gembuyer.in 180
9 Returning, Filling in including Spreading, Levelling, Watering and Well Ramming in Layers not exc. 250mm in Soft Loose Soil complete all as specified and as directed. Returning, Filling in, including Spreading, Levelling, Watering and Well Ramming in Layers not exc. 250mm in Soft/Loose Soil, complete all as specified and as directed. 146 Cum con688.ia.wb@gembuyer.in 180
10 Removing excavated Materials Soils not exc. 50.00 mtr and depositing where directed at a level not exc. 1.50 mtr above the Starting Point in Soil complete all as specified and as directed. Removing excavated Materials (Soils) not exc. 50.00 mtr and depositing where directed at a level not exc. 1.50 mtr above the Starting Point in Soil, complete all as specified and as directed. 94 Cum con688.ia.wb@gembuyer.in 180
11 M and L Sand Cushioning dry in Trenches for protection of UG Cables below above and around the UG Cable laid in Trenches of 230mm Spread thick ness etc. M&L Sand Cushioning (dry) in Trenches for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thick ness and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. (NOTE For the purpose of Payment, Punned thickness of Sand Cushioning only shall be Measured and Paid ). 79 CUM con688.ia.wb@gembuyer.in 180
12 Supply and laying fly ash brick locally available laid width wise across the line of cable in trenches for protection of UG cable complete all as specified and as directed. Supply and laying fly ash brick locally available laid width wise across the line of cable in trenches for protection of UG cable, complete all as specified and as directed. 7 Per 1000 Nos con688.ia.wb@gembuyer.in 180
13 S and F 50mm High density polyethylene pipe HDPE of pressure rating 6 kgf cm fixed complete to walls ceilings or in floors etc. complete all as specified and directed . S & F 50 mm High density polyethylene pipe (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc. complete all as specified and directed . 30 RM con688.ia.wb@gembuyer.in 180
14 S and F 40 mm High density polyethylene pipe HDPE of pressure rating 6 kgf cm fixed complete to walls ceilings or in floors etc. complete all as specified and directed . S & F 40 mm High density polyethylene pipe (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc. complete all as specified and directed . 18 RM con688.ia.wb@gembuyer.in 180
15 S and F Galvanised Iron Pipe 80mm Bore dia Light Grade for protection of UG Cable laid in Floors Road Crossing fixing to Pole with Mild Steel Clamps Nuts Bolts etc. S&F Galvanised Iron Pipe 80mm Bore (dia) Light Grade for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed. 36 RM con688.ia.wb@gembuyer.in 180
16 S and F Galvanised Iron Pipe 50mm Bore dia Light Grade for protection of UG Cable laid in Floors Road Crossing fixing to Pole with Mild Steel Clamps Nuts Bolts etc. S&F Galvanised Iron Pipe 50mm Bore (dia) Light Grade for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed. 12 RM con688.ia.wb@gembuyer.in 180
17 S and F Galvanised Iron Pipe 100mm Bore dia Light Grade for protection of UG Cable laid in Floors Road Crossing fixing to Pole with Mild Steel Clamps Nuts Bolts etc. S&F Galvanised Iron Pipe 100mm Bore (dia) Light Grade for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed. 18 RM con688.ia.wb@gembuyer.in 180
18 Labour only for Horizontal Boring for Passing Protection Pipe up to 80mm Bore dia under Road Foot Path not exc. 10.00 mtr in a Single Length complete all as specified and as directed. Labour only for Horizontal Boring for Passing Protection Pipe up to 80mm Bore (dia), under Road /Foot Path, not exc. 10.00 mtr in a Single Length, complete all as specified and as directed. Note. Pipe to be measured separately. 66 RM con688.ia.wb@gembuyer.in 180
19 Earthing of machinery equipment installed at power house sub station using 32x6mm galvanised MS strip and MS galvanised plate of size 600x600x6mm as earth electrode Earthing of machinery /equipment installed at power house/ sub station using 32x6mm galvanised MS strip and MS galvanised plate of size 600x600x6mm, as earth electrode 4 Set of 2 Earths con688.ia.wb@gembuyer.in 180
20 S and F of cubical housing cabinet type LT panel board outdoor type platform mounted factory made totally enclosed dust and vermin proof as per specification. S&F of cubical housing cabinet type LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 14 SWG (3.15mm) thick CRCA MS Sheet of overall size 1200 mm (height) x 1200 mm(width) 450 mm (depth) and built upon suitable size angle iron frame work , having front and rear hinged doors,GI earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply powder coated paint (RAL 7032) The panel should be suitable for 415 volts , 50Hz, 3 phase 4 wire system,with cable alley and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following, 1 Each con688.ia.wb@gembuyer.in 180
21 S and F of cubical housing cabinet type LT panel board outdoor type platform mounted factory made totally enclosed dust and vermin proof etc. S&F of cubical housing cabinet type LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 14 SWG (3.15mm) thick CRCA MS Sheet of overall size 1200 mm (height) x 1200 mm(width) 450 mm (depth) and built upon suitable size angle iron frame work , having front and rear hinged doors,GI earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply powder coated paint (RAL 7032) The panel should be suitable for 415 volts , 50Hz, 3 phase 4 wire system,with cable alley and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following. 1 Each con688.ia.wb@gembuyer.in 180
22 S and F of cubical housing cabinet type LT panel board outdoor type platform mounted factory made totally enclosed dust and vermin proof openable etc. S&F of cubical housing cabinet type LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 14 SWG (3.15mm) thick CRCA MS Sheet of overall size 1000mm (height) x 1200 mm(width) 450 mm (depth) and built upon suitable size angle iron frame work , having front and rear hinged doors,GI earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply powder coated paint (RAL7032) The panel should be suitable for 415 volts , 50Hz, 3 phase 4 wire system,with cable alley and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following 1 Each con688.ia.wb@gembuyer.in 180
23 S and F of cubical housing cabinet type LT panel board outdoor type platform mounted factory made totally enclosed dust and vermin proof openable from both side as per specification. S&F of cubical housing cabinet type LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 14 SWG (3.15mm) thick CRCA MS Sheet of overall size 1000 mm (height) x 1200 mm(width) 450 mm (depth) and built upon suitable size angle iron frame work , having front and rear hinged doors,GI earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply powder coated paint (RAL7032) The panel should be suitable for 415 volts , 50Hz, 3 phase 4 wire system,with cable alley and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following 1 Each con688.ia.wb@gembuyer.in 180
24 S and F sheet metal enclosures double door type VTPN DB 4 way for incorporating MCCBs upto 160 Amps MCB DP SP with busbarcomplete all as specified and directed. S&F sheet metal enclosures double door type VTPN DB 4 way for incorporating MCCBs upto 160 Amps,MCB DP,SP with busbar,complete all as specified and directed.Make ABB 11 Each con688.ia.wb@gembuyer.in 180
25 S and F sheet metal enclosures double door type VTPN DB 6 way for incorporating MCCBs upto 160 Amps,MCB DP,SP with busbar complete all as specified and directed. S&F sheet metal enclosures double door type VTPN DB 6 way for incorporating MCCBs upto 160 Amps,MCB DP,SP with busbar,complete all as specified and directed.Make ABB 1 Each con688.ia.wb@gembuyer.in 180
26 S and F MCCB 4 Pole 40 Amps breaking capacity 16 KA thermal and magnetic adjustable type 415 volts with extended copper terminals complete all as specified and directed. Supply and fixing MCCB 4 Pole 40 Amps, breaking capacity 16 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete all as specified and directed. 5 Each con688.ia.wb@gembuyer.in 180
27 S and F MCCB 4 Pole 63 Amps breaking capacity 16 KA thermal and magnetic adjustable type 415 volts with extended copper terminals complete all as specified and directed. Supply and fixing MCCB 4 Pole 63 Amps, breaking capacity 16 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete all as specified and directed. 6 Each con688.ia.wb@gembuyer.in 180
28 S and F MCCB 4 Pole 100 Amps breaking capacity 16 KA thermal and magnetic adjustable type 415 volts with extended copper terminals complete all as specified and directed. Supply and fixing MCCB 4 Pole 100 Amps, breaking capacity 16 KA, thermal & magnetic adjustable type, 415 volts with extended copper terminals complete all as specified and directed. 1 Each con688.ia.wb@gembuyer.in 180
29 S and F MCB SPN 32 Amps C series breaking capacity 10 Ka 415 Volts 50 Hz including necessary incoming and out going electric connection etc. S&F MCB SPN 32 Amps C series, breaking capacity 10 Ka, 415 Volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc complete all as specified and directed. 30 Each con688.ia.wb@gembuyer.in 180
30 S and F MCB SP 5 TO 32 Amps C series breaking capacity 10 Ka 415 Volts 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc. S&F MCB SP 5 TO 32 Amps C series, breaking capacity 10 Ka, 415 Volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc complete all as specified and directed. 90 Each con688.ia.wb@gembuyer.in 180
31 S and F sheet metal enclosures double door type SPN DB 8 way for incorporating MCBs complete all as specified and directed. S&F sheet metal enclosures double door type SPN DB 8 way for incorporating MCBs ,complete all as specified and directed. 15 Each con688.ia.wb@gembuyer.in 180
32 S and F sheet metal enclosures Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 20 Amp MCB complete all as specified and directed. S&F sheet metal enclosures Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 20 Amp MCB complete all as specified and directed. 80 Each con688.ia.wb@gembuyer.in 180
33 S and F sub main wiring with two run single core 4 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through and including suitable size PVC casing one single core 4 sqmm etc. Supply and fixing sub main wiring with two run single core 4 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through and including suitable size PVC casing caping (like Tee, Bend etc) complete fixed on wall/ceiling including one single core 4 sqmm copper earth continuity wire including assessories and cable copper lugs of suitable size for connecting to MCBs and connecting to earth complete, all as specified and as directed by EIC . 1800 RM con688.ia.wb@gembuyer.in 180
34 S and F sub main wiring with two run single core 6 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through etc. Supply and fixing sub main wiring with two run single core 6 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through and including suitable size PVC casing caping (like Tee, Bend etc) complete fixed on wall/ceiling including one single core 6 sqmm copper earth continuity wire including assessories and cable copper lugs of suitable size for connecting to MCBs and connecting to earth complete, all as specified and as directed by EIC . 100 RM con688.ia.wb@gembuyer.in 180
35 Earthing for poles and other machinery equipment using 4 mm GI wire as earthing lead and MS galvanized plate of size 60 cm x60 cm x6mm as earth electrode. Earthing for poles & other machinery/equipment using 4 mm GI wire as earthing lead and MS galvanized plate of size 60 cm x 60 cm x 6 mm, as earth electrode. 12 Each con688.ia.wb@gembuyer.in 180
36 Taking down out unserviceable or serviceable UG Cables of any Cross Sectional Area and Connections including Bricks GI Pipes etc. Taking down/out unserviceable or serviceable UG Cables of any Cross Sectional Area and Connections including Bricks, GI Pipes, etc. of any descriptions, laid in Trenches and/or fixing with Walls/Poles complete all as specified and as directed. 440 RM con688.ia.wb@gembuyer.in 180
37 Dismantling of Old LT feeder pillar boxes including demolishing PCC of base and filing the exacavated area for making flat surface complete all as spcified and as directed. Dismantling of Old LT feeder pillar boxes including demolishing PCC of base and filing the exacavated area for making flat surface, complete all as spcified and as directed. 1 Each con688.ia.wb@gembuyer.in 180